B42 PID Control Board

B42 Board Level High Performance PID Profile

Temperature Control

From $170 List

UL      CE  Rohs

 

Product Brochure & Pricing

B42_Series_Brochure.pdf

B42_Series_Price_Matrix.pdf

 

B42 Series Manual

B42_Series_Manual.pdf (744KB)

B42_CAD_Drawing_dwg.zip

 

Warranty: 3-Years

B Series 3-Year Warranty.pdf

 

Control Comparison: 100, 300, B, C, P, L & 90 Series

Single Loop Control Comparison.pdf (25KB)

 

Product Line Review Brochure:

FDC_Product_Line_Review.pdf (415KB)

 

SEL - User Configurable Display Prompts.htm

DIN Controls Standard Features.htm

DIN Controls Special Features.htm

DIN Control Alarm Configurations.htm

DIN Communication Accessories.htm

Additional Information

EnVision SCADA Software.html (FREE Software)

DIN Control Series - Feature Comparison.pdf

DIN Controls Output Module Part #.pdf

Price Sheet DIN Controls Output Modules.pdf

FDC-Set PC Configuration Software.htm

RS232/485 Converter for PC communication.pdf

 

Agency Approvals

UL Approval.pd

UL_CoC_B42_Control_Board.pdf

CE Conformity.pdf

EU_REACH Compliance.pdf

RoHS-3 Compliance.pdf

______________________________

 

Need single & multiloop controls and Data Acquisition system?

 

nCompass Series Operator Interface & Data Acquisition Systems for100/C, 300, B41, B42, L, & P Series Controls and FDC IO modules

nCompass Single & Multiloop Control System

Windows CE embedded Operator Interface and Data Acquisition offering 4.3" and 7" touch screen displays supporting up to 15 loop controls, 15 monitor points with up to 16 DI and 32 DO for user configurable control outputs, sequencing & logic.

Go to nCompass Page.htm

 

EnVision PC Based Data Acquisition

A FREE PC based SCADA software offers unrivaled flexibility for remote SCADA access to up to a mix of 128 devices.

 

Devices include Future Design Controls loop, IO and Orion-M iSeries control systems.

Go to EnVision Page.htm

 

Return to:

Main Products Page.htm

 

Based upon Future Design's dual display P41 Series Profile controls, the B42 board level profile PID control sets a new standard for board level controllers packed with performance to meet OEM needs for a single loop profiling control to communicate on a Serial modbus link.

The B42 is available with or without Display/Operator Interface Board. The optional Display Board has four buttons to change Setpoint and configuration parameters in the same fashion as the panel mount P41 Series . When used without the optional Display Board all setup & operator interface must be done through the optional Modbus communication port.

The B42, with up to 9 Profiles (up to 64 segments/profile), selection of PV inputs (18-bit), up to 4 control outputs, configurable Event input, PID Selection by Segment or Event input, PV/SP Retransmission (15-bit), serial Modbus RTU communication, fast scan rate (200ms), make it the right choice for a Profile control.

The B42 offers a full range of universal high resolution (18 bit) inputs; T/C, RTD and linear mA/VDC inputs. Power requirement of either 90-250 VAC or optional 11-26 VAC/VDC allows the B42 to be used virtually anywhere.

Note: The B42 is commonly used as a component in Future Design Controls nCompass LC control system.

___________________________________________________

Specification Review

  • 9 Programs with up to 64 Segments per program - see below
    • Programs 1 - 4 have up to 16 segments
    • Programs 5 - 7 have up to 32 segments
    • Programs 8 - 9 have up to 64 segments
  • Universal Process Input: T/C, RTD or specific Linear mA or VDC (all 18-bit)
  • Event Input: Configurable to Run, Hold, Run-Hold, Abort, Jump to next Segment, Select 2nd set of PID parameters, Failure Transfer (pre-configured output status), and Manual Mode.
  • Configurable: Security-Password, Time Base for Ramp and Soak, Configurable Hold-Back (Guarantee Soak & Ramp), Jump To Segment, Repeat, Start Profile Delay, Power Interruption Recovery and more.
  • Communication Options: RS232/485 Modbus & Retransmission.
  • Control Outputs - Up to 4 Control outputs & Communications:
    • Output #1: PID or on-off heat or cool control output (relay, ssr driver, triac or linear mA or VDC)
    • Output #2: PID or on-off cool control output (relay, ssr driver, triac or linear mA or VDC), or Alarm or Event output (relay, ssr driver or triac) or an Isolated Transmitter Power Supply.
    • Output #3: Alarm or Event output (relay, ssr driver or triac), or Isolated Transmitter Power Supply.
    • Output #4: Alarm or Event output (relay, ssr driver or triac), SP or PV Retransmission (mA or VDC) or Isolated Transmitter Power Supply.
    • Output #5: SP or PV Retransmission (mA or VDC), Isolated Transmitter Power Supply or Modbus RTU RS485 or RS232.
    • Note: all linear mA & VDC outputs are 15-bit.
  • Program Control Configuration Options
    • Up to 9 Programs with up to 64 segments (see above)
    • Global Program Settings: Starting & Ending Setpoint Values for Program
      • Delayed Program Start time in hh:mm
      • Power Fail / Recovery logic: Continue from last SP, Continue from current PV, Static Mode SP1, Static mode Start SP (see above) and OFF.
      • Holdback Wait Time (Guaranteed Soak/Ramp maximum hold time before program continue).
    • Configurable per Segment Target SP for Ramp segment and Start SP/Final SP values for segment configured as ramp in units/minute or hour.
      • Final SP for end segment
      • Event Outputs (up to 3 for P41 and 2 for P91) and selection of xxxxxxxxxxx PID set #1 or #2.
      • Time unit & duration for ramp & dwell: hh.mm, mm.ss and for ramp configurable units/minute or units/hour (0.0 to 900.0F/minute or hour).
      • Holdback band and control action: Off, Low deviation, High deviation or Deviation band. (Holdback is also known as Guaranteed Soak / Ramp.)
      • Segment Jump and number or Repeat Cycles.

___________________________________________________

Technical Specifications

  • Power Input:
    • 90-250VAC, 47-630hz,12VA, 5W maximum
    • 11-26VDC/VAC, 12VA, 5W maximum is optional
  • Inputs:
    • Universal Process Input:
      • Thermocouple: Types J, K, T, E, B, R, S, N, L, C & P
      • RTD: PT 100 ohm DIN and PT 100 JIS
      • Linear: 0-60mV, 1-5VDC, 0-5VDC, 0-10VDC and 0-20/4-20mA input (mA input special hardware order code)
    • Event Input: Dry Contact configurable to Run, Hold, Abort, Jump to next Segment within a profile, Manual Mode, Failure Transfer (pre-configured output status), Off (all outputs off) and selection of PID#2.. 
  • Input sample rate: 5 scans/second
  • Input Resolution: 18 Bit [262,144] click here for 18 Bit descr.
  • Control Outputs: Up to 2 isolated PID control outputs; to have two PID outputs #1 must be PID & output #2 is default PID Cool. Available hardware outputs are:
    • relay 2A/240 VAC resistive (SPST)
    • ssr driver - 5VDC/30mA or 14VDC/40mA
    • triac 1A/240VAC
    • 4-20/0-20mA* into 500 ohms
    • 1-5/0-5VDC* or 1-10/0-10VDC*
      • * linear outputs are 15-bit
  • Alarm or Event Outputs: The P41 has up to 3 and the P91 up to 2 configurable alarm or event outputs when Output #2 configured as an alarm or event. When Output #2 is a PID control output the P41 has up to 2 and the P91 has one alarm or event outputs. Available hardware for output #3 and specific to the P41output #4.
    •  relay 2A/240 VAC resistive (SPST except P41 output#3 SPDT)
    • ssr driver - 5VDC/30mA or 14VDC/40mA
    • triac 1A/240VAC
  • Retransmission PV or SP: (retrans outputs are 15-bit)
    • 0-20/4-20mA or 0-5/1-5VDC is available in lieu of alarm/event output #4 specific to the P41 output #5.
    • Multi-zone programming can be implemented by using SP retransmission to deliver a master setpoint to one, two, three or more client controllers with holdback from any client if PV deviates from SP value by more than a set value per client controller (deviation or deviation band alarm/client wired to event input on P41/91).
  • Transmitter Power Supply [isolated] is available in lieu of control or alarm/event outputs; #2, # 3 & #4 and specific to the P41, output #5
  • Communications RS232/485 Modbus
  • Security: Software configurable
    • None: All parameters are unlocked
    • Password (0-9999) configurable
      • Without password no parameters may be changed.
      • With password all parameters are changeable
      • With password only Home Page (SEL) may be changed.
    • Set: Setup Configuration Data is locked
    • User: All data locked except SP#1 and alarms #1, #2 and #3. [total 4 outputs]
    • All: All data locked